Tap Water Lookup

EPA system FL4560954 · Florida

Port St Lucie Utilities: No PFAS or lithium found in EPA testing

System ID FL4560954; community water system; Florida; source: groundwater; serves 224,485 people via 89,794 connections; status: active

In focus224,485people served, EPA registry
Public records. Clearer context.
Highest result against its EPA referenceLead, 90th percentile at customer taps
Lead, 90th percentile at customer taps: 4.6 ppb; action level 15 ppb. 90th percentile for the latest monitoring period.4.6 ppbaction level: 15 ppb

90th percentile for the latest monitoring period; sampled Dec 1, 2023. Source: EPA SDWIS/ECHO.

Port St Lucie Utilities is a local-government-owned community water system in Florida serving about 224,485 people, matched to 12 ZIP codes.

< 4.0 ppt
PFOA, highest complete-set average
4 samples, none above the reporting level
MCL 4.0 ppt · not detected above the reporting level
< 4.0 ppt
PFOS, highest complete-set average
4 samples, none above the reporting level
MCL 4.0 ppt · not detected above the reporting level
< 9 ppb
Lithium, highest single sample
4 samples, none above the reporting level
health reference level 10 ppb · not detected above the reporting level
0 / 29
PFAS found above the reporting level
120 results, 2 entry points
0 at or above an MCL on the average basis
4.6 ppb
Lead 90th percentile
period ending Dec 1, 2023
action level 15 ppb · below the action level
0
health-based violations since Sep 3, 2016
35 violations in total

PFAS treatment declared to EPA: None declared (2 of 2 sampling events) · PFAS found before UCMR 5: Yes, at 2 of 4 sampling events

PFAS and lithium: what EPA's national survey found

EPA tested this water for 30 substances and found none of them at levels its laboratories can measure.

Between March 2025 and September 2025, EPA's UCMR 5 program tested 120 samples from 2 sampling locations for 30 contaminants (29 PFAS plus lithium). None were found above their minimum reporting levels.

Result EPA comparesNot detected, shown at the reporting levelEPA reference value, at the middle of each row's scale
ContaminantResult against the EPA referenceResultStatus
No contaminant was detected above its reporting level.
Show the 30 contaminants not detected above the reporting level
11Cl-PF3OUdSnot detected · reporting level 5.0 ppt
< 5.0 ppt
not detected above the reporting level
4:2 FTSnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
6:2 FTSnot detected · reporting level 5.0 ppt
< 5.0 ppt
not detected above the reporting level
8:2 FTSnot detected · reporting level 5.0 ppt
< 5.0 ppt
not detected above the reporting level
9Cl-PF3ONSnot detected · reporting level 2.0 ppt
< 2.0 ppt
not detected above the reporting level
ADONAnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
HFPO-DA (GenX)not detected · reporting level 5.0 ppt
< 5.0 ppt
not detected above the reporting level
Lithiumnot detected · reporting level 9 ppb
< 9 ppb
not detected above the reporting level
NEtFOSAAnot detected · reporting level 5.0 ppt
< 5.0 ppt
not detected above the reporting level
NFDHAnot detected · reporting level 20.0 ppt
< 20.0 ppt
not detected above the reporting level
NMeFOSAAnot detected · reporting level 6.0 ppt
< 6.0 ppt
not detected above the reporting level
PFBAnot detected · reporting level 5.0 ppt
< 5.0 ppt
not detected above the reporting level
PFBSnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
PFDAnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
PFDoAnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
PFEESAnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
PFHpAnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
PFHpSnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
PFHxAnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
PFHxSnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
PFMBAnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
PFMPAnot detected · reporting level 4.0 ppt
< 4.0 ppt
not detected above the reporting level
PFNAnot detected · reporting level 4.0 ppt
< 4.0 ppt
not detected above the reporting level
PFOAnot detected · reporting level 4.0 ppt
< 4.0 ppt
not detected above the reporting level
PFOSnot detected · reporting level 4.0 ppt
< 4.0 ppt
not detected above the reporting level
PFPeAnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
PFPeSnot detected · reporting level 4.0 ppt
< 4.0 ppt
not detected above the reporting level
PFTAnot detected · reporting level 8.0 ppt
< 8.0 ppt
not detected above the reporting level
PFTrDAnot detected · reporting level 7.0 ppt
< 7.0 ppt
not detected above the reporting level
PFUnAnot detected · reporting level 2.0 ppt
< 2.0 ppt
not detected above the reporting level
Full table: samples, detections, highest single sample, complete-set average and sampling dates for all 30 contaminants
ContaminantSamplesDetectionsHighest single sampleComplete-set average (results used)EPA referenceStatusSampled
11Cl-PF3OUdS40< 5.0 pptnone setnot detected above the reporting levelMarch 2025 – September 2025
4:2 FTS40< 3.0 pptnone setnot detected above the reporting levelMarch 2025 – September 2025
6:2 FTS40< 5.0 pptnone setnot detected above the reporting levelMarch 2025 – September 2025
8:2 FTS40< 5.0 pptnone setnot detected above the reporting levelMarch 2025 – September 2025
9Cl-PF3ONS40< 2.0 pptnone setnot detected above the reporting levelMarch 2025 – September 2025
ADONA40< 3.0 pptnone setnot detected above the reporting levelMarch 2025 – September 2025
HFPO-DA (GenX)40< 5.0 ppt10.0 ppt MCL (rescission proposed) · compared on the complete-set averagenot detected above the reporting levelMarch 2025 – September 2025
Lithium40< 9 ppb10 ppb health reference level · compared on the highest samplenot detected above the reporting levelMarch 2025 – September 2025
NEtFOSAA40< 5.0 pptnone setnot detected above the reporting levelMarch 2025 – September 2025
NFDHA40< 20.0 pptnone setnot detected above the reporting levelMarch 2025 – September 2025
NMeFOSAA40< 6.0 pptnone setnot detected above the reporting levelMarch 2025 – September 2025
PFBA40< 5.0 ppt6,000 ppt screening level · compared on the highest samplenot detected above the reporting levelMarch 2025 – September 2025
PFBS40< 3.0 ppt2,000 ppt health-based water concentration · compared on the highest samplenot detected above the reporting levelMarch 2025 – September 2025
PFDA40< 3.0 pptnone setnot detected above the reporting levelMarch 2025 – September 2025
PFDoA40< 3.0 pptnone setnot detected above the reporting levelMarch 2025 – September 2025
PFEESA40< 3.0 pptnone setnot detected above the reporting levelMarch 2025 – September 2025
PFHpA40< 3.0 pptnone setnot detected above the reporting levelMarch 2025 – September 2025
PFHpS40< 3.0 pptnone setnot detected above the reporting levelMarch 2025 – September 2025
PFHxA40< 3.0 ppt3,000 ppt screening level · compared on the highest samplenot detected above the reporting levelMarch 2025 – September 2025
PFHxS40< 3.0 ppt10.0 ppt MCL (rescission proposed) · compared on the complete-set averagenot detected above the reporting levelMarch 2025 – September 2025
PFMBA40< 3.0 pptnone setnot detected above the reporting levelMarch 2025 – September 2025
PFMPA40< 4.0 pptnone setnot detected above the reporting levelMarch 2025 – September 2025
PFNA40< 4.0 ppt10.0 ppt MCL (rescission proposed) · compared on the complete-set averagenot detected above the reporting levelMarch 2025 – September 2025
PFOA40< 4.0 ppt4.0 ppt MCL · compared on the complete-set averagenot detected above the reporting levelMarch 2025 – September 2025
PFOS40< 4.0 ppt4.0 ppt MCL · compared on the complete-set averagenot detected above the reporting levelMarch 2025 – September 2025
PFPeA40< 3.0 pptnone setnot detected above the reporting levelMarch 2025 – September 2025
PFPeS40< 4.0 pptnone setnot detected above the reporting levelMarch 2025 – September 2025
PFTA40< 8.0 pptnone setnot detected above the reporting levelMarch 2025 – September 2025
PFTrDA40< 7.0 pptnone setnot detected above the reporting levelMarch 2025 – September 2025
PFUnA40< 2.0 pptnone setnot detected above the reporting levelMarch 2025 – September 2025
UCMR 5 is a one-time national monitoring survey. Its results do not indicate compliance or non-compliance with the PFAS Maximum Contaminant Levels, which are enforced on running annual averages and take effect in 2029 (EPA has proposed allowing extensions to 2031). A single result above a limit on this page is a measurement, not a violation.

Sampling-point average: mean of a location's two (ground water) or four (surface water) UCMR 5 results with non-detects counted as zero, EPA's method for comparing UCMR 5 data to the PFAS MCLs. EPA rounds to the reference value's significant digits before deciding whether an average is "greater than" an MCL (PFOA/PFOS averages count as above 4.0 ng/L only from 4.05 ng/L; lithium results count as above the 10 ppb reference only from 15 ppb). This site does not apply that rounding: "at or above" here means the measured value is numerically at or above the reference.

Utility-reported context (UCMR 5 questionnaire, aggregated across sampling events): PFAS previously found at this system: yes at 2 of 4 sampling events, not known at 2 of 4 sampling events; potential PFAS sources nearby: no at 2 of 4 sampling events, not known at 2 of 4 sampling events; PFAS treatment in place: no PFAS treatment at 2 of 2 sampling events.

Lead at customer taps

In the latest completed monitoring period, ending Dec 1, 2023, 9 in 10 sampled homes had lead at or below 4.6 ppb, below the 15 ppb action level that triggers utility action. The action level has been reached in 4 of the 26 periods on record.

Action level 15 ppb015Jan 1, 2009 – Dec 1, 2009: 2.8 ppbJan 1, 2010 – Jun 1, 2010: 4.5 ppbJul 1, 2010 – Dec 1, 2010: 4.1 ppbJan 1, 2011 – Jun 1, 2011: 3.1 ppbJan 1, 2012 – Dec 1, 2012: 1.9 ppbJan 1, 2013 – Dec 1, 2013: 3 ppbJan 1, 2014 – Dec 1, 2014: 3.1 ppbJan 1, 2015 – Dec 1, 2015: 1.9 ppbJan 1, 2016 – Dec 1, 2016: 4.7 ppbJan 1, 2017 – Dec 1, 2017: 3.7 ppbJan 1, 2020 – Dec 1, 2020: 1.9 ppbJan 1, 2023 – Dec 1, 2023: 4.6 ppbDec 1, 2009Dec 1, 20234.6 ppb

In the most recent completed lead monitoring period, ending Dec 1, 2023, the 90th-percentile lead result at customer taps was 4.6 ppb, below the action level of 15 ppb; 4 of the 26 monitoring periods on record reached the action level. The 90th percentile is the value that 9 in 10 sampled homes were at or below. Values are in parts per billion (ppb).

Monitoring periodMetal90th percentileAction levelStatus
Jan 1, 2023 – Dec 1, 2023Lead4.6 ppb15 ppbbelow the action level
Jan 1, 2020 – Dec 1, 2020Lead1.9 ppb15 ppbbelow the action level
Jan 1, 2017 – Dec 1, 2017Lead3.7 ppb15 ppbbelow the action level
Jan 1, 2016 – Dec 1, 2016Lead4.7 ppb15 ppbbelow the action level
Jan 1, 2015 – Dec 1, 2015Lead1.9 ppb15 ppbbelow the action level
Jan 1, 2014 – Dec 1, 2014Lead3.1 ppb15 ppbbelow the action level
Jan 1, 2013 – Dec 1, 2013Lead3 ppb15 ppbbelow the action level
Jan 1, 2012 – Dec 1, 2012Lead1.9 ppb15 ppbbelow the action level
Jan 1, 2011 – Jun 1, 2011Lead3.1 ppb15 ppbbelow the action level
Jul 1, 2010 – Dec 1, 2010Lead4.1 ppb15 ppbbelow the action level
Jan 1, 2010 – Jun 1, 2010Lead4.5 ppb15 ppbbelow the action level
Jan 1, 2009 – Dec 1, 2009Lead2.8 ppb15 ppbbelow the action level
Show all 26 monitoring periods on record
Monitoring periodMetal90th percentileAction levelStatus
Jan 1, 2023 – Dec 1, 2023Lead4.6 ppb15 ppbbelow the action level
Jan 1, 2020 – Dec 1, 2020Lead1.9 ppb15 ppbbelow the action level
Jan 1, 2017 – Dec 1, 2017Lead3.7 ppb15 ppbbelow the action level
Jan 1, 2016 – Dec 1, 2016Lead4.7 ppb15 ppbbelow the action level
Jan 1, 2015 – Dec 1, 2015Lead1.9 ppb15 ppbbelow the action level
Jan 1, 2014 – Dec 1, 2014Lead3.1 ppb15 ppbbelow the action level
Jan 1, 2013 – Dec 1, 2013Lead3 ppb15 ppbbelow the action level
Jan 1, 2012 – Dec 1, 2012Lead1.9 ppb15 ppbbelow the action level
Jan 1, 2011 – Jun 1, 2011Lead3.1 ppb15 ppbbelow the action level
Jul 1, 2010 – Dec 1, 2010Lead4.1 ppb15 ppbbelow the action level
Jan 1, 2010 – Jun 1, 2010Lead4.5 ppb15 ppbbelow the action level
Jan 1, 2009 – Dec 1, 2009Lead2.8 ppb15 ppbbelow the action level
Jan 1, 2008 – Dec 1, 2008Lead2.4 ppb15 ppbbelow the action level
Jan 1, 2007 – Dec 1, 2007Lead10 ppb15 ppbbelow the action level
Jan 1, 2006 – Jun 1, 2006Lead4 ppb15 ppbbelow the action level
Jan 1, 2003 – Dec 31, 2003Lead6.1 ppb15 ppbbelow the action level
Jan 1, 2002 – Dec 31, 2002Lead5 ppb15 ppbbelow the action level
Jul 1, 2001 – Dec 31, 2001Lead6.8 ppb15 ppbbelow the action level
Jan 1, 2001 – Jun 30, 2001Lead7.3 ppb15 ppbbelow the action level
Jul 1, 2000 – Dec 31, 2000Lead8.4 ppb15 ppbbelow the action level
Jan 1, 2000 – Jun 30, 2000Lead60 ppb15 ppbat or above the action level
Jan 1, 1999 – Dec 31, 1999Lead31 ppb15 ppbat or above the action level
Jan 1, 1998 – Jun 30, 1998Lead7.9 ppb15 ppbbelow the action level
Jul 1, 1997 – Dec 31, 1997Lead12 ppb15 ppbbelow the action level
Jan 1, 1993 – Jun 30, 1993Lead25 ppb15 ppbat or above the action level
Jul 1, 1992 – Dec 31, 1992Lead41 ppb15 ppbat or above the action level

Drinking water violations since Sep 3, 2016

EPA lists 35 violations since Sep 3, 2016. None is health-based. All concern missed monitoring, reporting or public notices, not the water itself. 1 is still open.

EPA's SDWIS database lists 35 violations recorded since Sep 3, 2016: 34 for monitoring or reporting, 1 other (public notification or consumer confidence report requirements), none health-based; 1 is not yet resolved.

Compliance periodTypeContaminant / ruleDescriptionRecordsStatus
Mar 1, 2026 – Mar 31, 2026MONRevised Total Coliform RuleMonitoring, Routine (RTCR)1 recordArchived
Feb 1, 2026 – Feb 28, 2026MONRevised Total Coliform RuleMonitoring, Routine (RTCR)1 recordArchived
Jan 1, 2026 – Jan 31, 2026MONRevised Total Coliform RuleMonitoring, Routine (RTCR)1 recordArchived
Aug 1, 2025 – Aug 31, 2025MONRevised Total Coliform RuleMonitoring, Routine (RTCR)1 recordArchived
Jul 1, 2025 – Jul 31, 2025MONRevised Total Coliform RuleMonitoring, Routine (RTCR)1 recordArchived
Jul 1, 2025OtherConsumer Confidence RuleConsumer Confidence Report Complete Failure to Report1 recordUnaddressed
Apr 1, 2025 – Apr 30, 2025MONRevised Total Coliform RuleMonitoring, Routine (RTCR)1 recordArchived
Mar 1, 2025 – Mar 31, 2025MONRevised Total Coliform RuleMonitoring, Routine (RTCR)1 recordArchived
Feb 1, 2025 – Feb 28, 2025MONRevised Total Coliform RuleMonitoring, Routine (RTCR)1 recordArchived
Jan 1, 2025 – Mar 31, 2025MRTotal Haloacetic Acids (Haa5)Monitoring and Reporting (DBP)1 recordArchived
Jan 1, 2025 – Dec 31, 2025MRNitrateMonitoring, Regular1 recordArchived
Jan 1, 2025 – Mar 31, 2025MRTthmMonitoring and Reporting (DBP)1 recordArchived
Jan 1, 2025 – Jan 31, 2025MONRevised Total Coliform RuleMonitoring, Routine (RTCR)1 recordArchived
Dec 1, 2024 – Dec 31, 2024MONRevised Total Coliform RuleMonitoring, Routine (RTCR)1 recordResolved · 1 enforcement action
Nov 1, 2024 – Nov 30, 2024MONRevised Total Coliform RuleMonitoring, Routine (RTCR)1 recordResolved · 1 enforcement action
Oct 1, 2024 – Oct 31, 2024MONRevised Total Coliform RuleMonitoring, Routine (RTCR)1 recordResolved · 1 enforcement action
Oct 1, 2024 – Dec 31, 2024MRTthmMonitoring and Reporting (DBP)1 recordArchived
Oct 1, 2024 – Dec 31, 2024MRTotal Haloacetic Acids (Haa5)Monitoring and Reporting (DBP)1 recordArchived
Sep 1, 2024 – Sep 30, 2024MONRevised Total Coliform RuleMonitoring, Routine (RTCR)1 recordResolved · 1 enforcement action
Aug 1, 2024 – Aug 31, 2024MONRevised Total Coliform RuleMonitoring, Routine (RTCR)1 recordResolved · 1 enforcement action
Jul 1, 2024 – Sep 30, 2024MRTotal Haloacetic Acids (Haa5)Monitoring and Reporting (DBP)1 recordArchived
Jul 1, 2024 – Sep 30, 2024MRTthmMonitoring and Reporting (DBP)1 recordArchived
Jul 1, 2024 – Jul 31, 2024MONRevised Total Coliform RuleMonitoring, Routine (RTCR)1 recordArchived
Jan 1, 2024 – Jan 31, 2024MONRevised Total Coliform RuleMonitoring, Routine (RTCR)1 recordResolved · 1 enforcement action
Jan 1, 2024 – Dec 31, 2024MRNitrateMonitoring, Regular1 recordResolved · 1 enforcement action
Show the remaining 10 violation records
Compliance periodTypeContaminant / ruleDescriptionRecordsStatus
Dec 1, 2023 – Dec 31, 2023MONRevised Total Coliform RuleMonitoring, Routine (RTCR)1 recordResolved
Nov 1, 2023 – Nov 30, 2023MONRevised Total Coliform RuleMonitoring, Routine (RTCR)1 recordResolved
Oct 1, 2023 – Dec 31, 2023MRTotal Haloacetic Acids (Haa5)Monitoring and Reporting (DBP)1 recordArchived
Oct 1, 2023 – Dec 31, 2023MRTthmMonitoring and Reporting (DBP)1 recordArchived
Jun 1, 2023 – Jun 30, 2023MONRevised Total Coliform RuleMonitoring, Routine (RTCR)1 recordResolved
Apr 1, 2023 – Jun 30, 2023MRTotal Haloacetic Acids (Haa5)Monitoring and Reporting (DBP)1 recordArchived
Apr 1, 2023 – Jun 30, 2023MRTthmMonitoring and Reporting (DBP)1 recordArchived
Sep 1, 2021RPTRevised Total Coliform RuleReporting, Assessment Forms (RTCR)1 recordResolved
Jul 1, 2019RPTRevised Total Coliform RuleReporting, Assessment Forms (RTCR)1 recordResolved
Jun 1, 2019RPTRevised Total Coliform RuleReporting, Assessment Forms (RTCR)1 recordResolved

Sanitary surveys and site visits

Most recent state inspection: Jul 12, 2023 (sanitary survey); 1 visit since Sep 3, 2021.

What you can do about these results

Filters certified for lead reduction

4 of this utility's 26 lead monitoring periods on record reached the 15 ppb action level (most recent 90th percentile 4.6 ppb).

NSF/ANSI 53 with a lead-reduction claim, or NSF/ANSI 58 reverse osmosis. Lead comes from plumbing, so a point-of-use filter at the kitchen tap is the relevant type.

ZIP codes served

Sources

Data vintage: EPA UCMR 5 occurrence data, samples collected 2023-01-03 – 2026-06-17, final release, August 2026 (file dated Aug 28, 2026); EPA SDWIS via ECHO, 2026Q2 extract (file dated Jul 9, 2026); EPA service-area boundaries v3.0; Census 2020 ZCTAs. Page generated 2026-09-03.

Keep exploring

Every record tells
part of the story.

Find a place. Read the measurements.
Understand the context.

Explore water records