Tap Water Lookup

EPA system GA2450000 · Georgia

Augusta-Richmond Co Ws: PFOS at or above EPA's 4.0 ppt limit

System ID GA2450000; community water system; Georgia; source: surface water; serves 204,000 people via 78,500 connections; status: active

In focus204,000people served, EPA registry
Public records. Clearer context.
Highest result against its EPA referencePFOS
PFOS: 43.6 ppt; MCL 4.0 ppt. highest complete sampling-location average.43.6 pptMCL: 4.0 ppt

highest complete sampling-location average; sampled June 2023–March 2024. Source: EPA UCMR 5 final release, August 2026.

Augusta-Richmond Co Ws is a local-government-owned community water system in Georgia serving about 204,000 people, matched to 7 ZIP codes.

26.6 ppt
PFOA, highest complete-set average
2 of 2 results at the highest location; highest single sample 29.9 ppt
MCL 4.0 ppt · at or above the MCL
43.6 ppt
PFOS, highest complete-set average
2 of 2 results at the highest location; highest single sample 51.0 ppt
MCL 4.0 ppt · at or above the MCL
< 9 ppb
Lithium, highest single sample
14 samples, none above the reporting level
health reference level 10 ppb · not detected above the reporting level
7 / 29
PFAS found above the reporting level
420 results, 5 entry points
3 at or above an MCL on the average basis
1.4 ppb
Lead 90th percentile
period ending Dec 31, 2025
action level 15 ppb · below the action level
0
health-based violations since Sep 3, 2016
0 violations in total

PFAS treatment declared to EPA: None declared (14 of 14 sampling events) · PFAS found before UCMR 5: Yes, at 14 of 14 sampling events

What EPA says about what was found

  • PFOS EPA set the health goal (MCLG) for PFOS at zero. EPA's 2024 rule cites its health effects assessment linking PFOS exposure to certain cancers, immune and developmental effects, and changes in cholesterol. EPA source
  • PFOA EPA set the health goal (MCLG) for PFOA at zero. EPA's 2024 rule cites its health effects assessment linking PFOA exposure to certain cancers, immune and developmental effects, and changes in cholesterol. EPA source
  • PFHxS EPA's 2024 rule cites health effects assessments associating PFHxS with thyroid, liver and immune effects. EPA source
  • PFHxA EPA's 2023 IRIS assessment for PFHxA cites developmental, liver and blood effects in animal studies. EPA source

Quoted from EPA assessments. This site adds no health claims of its own.

PFAS and lithium: what EPA's national survey found

EPA tested this water for 30 substances and found 7. PFOA averaged 26.6 ppt where EPA's limit is 4.0 ppt, and PFOS averaged 43.6 ppt where EPA's limit is 4.0 ppt. EPA's limit applies to a running yearly average and is enforced from 2029. That PFOS result is higher than 99.8% of the 10,307 water systems EPA tested for it.

Between June 2023 and March 2024, EPA's UCMR 5 program tested 420 samples from 5 sampling locations for 30 contaminants (29 PFAS plus lithium). 7 were detected above the reporting level in at least one sample. Averaged over a complete monitoring set, the highest sampling location for PFOA was 26.6 ppt, at or above the MCL of 4.0 ppt that applies from 2029 (highest single sample 29.9 ppt). Averaged over a complete monitoring set, the highest sampling location for PFOS was 43.6 ppt, at or above the MCL of 4.0 ppt that applies from 2029 (highest single sample 51.0 ppt).

Result EPA comparesNot detected, shown at the reporting levelEPA reference value, at the middle of each row's scale
ContaminantResult against the EPA referenceResultStatus
PFOScomplete-set average
43.6 ppt
at or above the MCL
PFOAcomplete-set average
26.6 ppt
at or above the MCL
PFHxScomplete-set average
44.5 ppt
at or above the 2024 MCL (rescission proposed)
PFPeShighest single sample
5.4 ppt
detected; no EPA reference value
PFPeAhighest single sample
3.0 ppt
detected; no EPA reference value
PFHxAhighest single sample
9.0 ppt
below the screening level
PFBShighest single sample
5.9 ppt
below the health-based water concentration
Show the 23 contaminants not detected above the reporting level
11Cl-PF3OUdSnot detected · reporting level 5.0 ppt
< 5.0 ppt
not detected above the reporting level
4:2 FTSnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
6:2 FTSnot detected · reporting level 5.0 ppt
< 5.0 ppt
not detected above the reporting level
8:2 FTSnot detected · reporting level 5.0 ppt
< 5.0 ppt
not detected above the reporting level
9Cl-PF3ONSnot detected · reporting level 2.0 ppt
< 2.0 ppt
not detected above the reporting level
ADONAnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
HFPO-DA (GenX)not detected · reporting level 5.0 ppt
< 5.0 ppt
not detected above the reporting level
Lithiumnot detected · reporting level 9 ppb
< 9 ppb
not detected above the reporting level
NEtFOSAAnot detected · reporting level 5.0 ppt
< 5.0 ppt
not detected above the reporting level
NFDHAnot detected · reporting level 20.0 ppt
< 20.0 ppt
not detected above the reporting level
NMeFOSAAnot detected · reporting level 6.0 ppt
< 6.0 ppt
not detected above the reporting level
PFBAnot detected · reporting level 5.0 ppt
< 5.0 ppt
not detected above the reporting level
PFDAnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
PFDoAnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
PFEESAnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
PFHpAnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
PFHpSnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
PFMBAnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
PFMPAnot detected · reporting level 4.0 ppt
< 4.0 ppt
not detected above the reporting level
PFNAnot detected · reporting level 4.0 ppt
< 4.0 ppt
not detected above the reporting level
PFTAnot detected · reporting level 8.0 ppt
< 8.0 ppt
not detected above the reporting level
PFTrDAnot detected · reporting level 7.0 ppt
< 7.0 ppt
not detected above the reporting level
PFUnAnot detected · reporting level 2.0 ppt
< 2.0 ppt
not detected above the reporting level
Full table: samples, detections, highest single sample, complete-set average and sampling dates for all 30 contaminants
ContaminantSamplesDetectionsHighest single sampleComplete-set average (results used)EPA referenceStatusSampled
PFOS14451.0 ppt43.6 ppt (2 of 2)4.0 ppt MCL · compared on the complete-set averageat or above the MCLJune 2023 – March 2024
PFOA14229.9 ppt26.6 ppt (2 of 2)4.0 ppt MCL · compared on the complete-set averageat or above the MCLJune 2023 – March 2024
PFHxS14451.2 ppt44.5 ppt (2 of 2)10.0 ppt MCL (rescission proposed) · compared on the complete-set averageat or above the 2024 MCL (rescission proposed)June 2023 – March 2024
PFPeS1425.4 ppt4.8 ppt (2 of 2)none setdetected; no EPA reference valueJune 2023 – March 2024
PFPeA1423.0 ppt0.8 ppt (4 of 4)none setdetected; no EPA reference valueJune 2023 – March 2024
PFHxA1429.0 ppt7.9 ppt (2 of 2)3,000 ppt screening level · compared on the highest samplebelow the screening levelJune 2023 – March 2024
PFBS1425.9 ppt5.1 ppt (2 of 2)2,000 ppt health-based water concentration · compared on the highest samplebelow the health-based water concentrationJune 2023 – March 2024
11Cl-PF3OUdS140< 5.0 pptnone setnot detected above the reporting levelJune 2023 – March 2024
4:2 FTS140< 3.0 pptnone setnot detected above the reporting levelJune 2023 – March 2024
6:2 FTS140< 5.0 pptnone setnot detected above the reporting levelJune 2023 – March 2024
8:2 FTS140< 5.0 pptnone setnot detected above the reporting levelJune 2023 – March 2024
9Cl-PF3ONS140< 2.0 pptnone setnot detected above the reporting levelJune 2023 – March 2024
ADONA140< 3.0 pptnone setnot detected above the reporting levelJune 2023 – March 2024
HFPO-DA (GenX)140< 5.0 ppt10.0 ppt MCL (rescission proposed) · compared on the complete-set averagenot detected above the reporting levelJune 2023 – March 2024
Lithium140< 9 ppb10 ppb health reference level · compared on the highest samplenot detected above the reporting levelJune 2023 – March 2024
NEtFOSAA140< 5.0 pptnone setnot detected above the reporting levelJune 2023 – March 2024
NFDHA140< 20.0 pptnone setnot detected above the reporting levelJune 2023 – March 2024
NMeFOSAA140< 6.0 pptnone setnot detected above the reporting levelJune 2023 – March 2024
PFBA140< 5.0 ppt6,000 ppt screening level · compared on the highest samplenot detected above the reporting levelJune 2023 – March 2024
PFDA140< 3.0 pptnone setnot detected above the reporting levelJune 2023 – March 2024
PFDoA140< 3.0 pptnone setnot detected above the reporting levelJune 2023 – March 2024
PFEESA140< 3.0 pptnone setnot detected above the reporting levelJune 2023 – March 2024
PFHpA140< 3.0 pptnone setnot detected above the reporting levelJune 2023 – March 2024
PFHpS140< 3.0 pptnone setnot detected above the reporting levelJune 2023 – March 2024
PFMBA140< 3.0 pptnone setnot detected above the reporting levelJune 2023 – March 2024
PFMPA140< 4.0 pptnone setnot detected above the reporting levelJune 2023 – March 2024
PFNA140< 4.0 ppt10.0 ppt MCL (rescission proposed) · compared on the complete-set averagenot detected above the reporting levelJune 2023 – March 2024
PFTA140< 8.0 pptnone setnot detected above the reporting levelJune 2023 – March 2024
PFTrDA140< 7.0 pptnone setnot detected above the reporting levelJune 2023 – March 2024
PFUnA140< 2.0 pptnone setnot detected above the reporting levelJune 2023 – March 2024
UCMR 5 is a one-time national monitoring survey. Its results do not indicate compliance or non-compliance with the PFAS Maximum Contaminant Levels, which are enforced on running annual averages and take effect in 2029 (EPA has proposed allowing extensions to 2031). A single result above a limit on this page is a measurement, not a violation.

Sampling-point average: mean of a location's two (ground water) or four (surface water) UCMR 5 results with non-detects counted as zero, EPA's method for comparing UCMR 5 data to the PFAS MCLs. EPA rounds to the reference value's significant digits before deciding whether an average is "greater than" an MCL (PFOA/PFOS averages count as above 4.0 ng/L only from 4.05 ng/L; lithium results count as above the 10 ppb reference only from 15 ppb). This site does not apply that rounding: "at or above" here means the measured value is numerically at or above the reference.

Every detection by sampling location (18 results)
DateSampling locationSource waterContaminantResultReporting level
Jun 22, 2023Finished Water Tap Bush Field Plantground waterPFBS5.9 ppt3.0 ppt
Jun 22, 2023Finished Water Tap Bush Field Plantground waterPFHxA9.0 ppt3.0 ppt
Jun 22, 2023Finished Water Tap Bush Field Plantground waterPFHxS51.2 ppt3.0 ppt
Jun 22, 2023Finished Water Tap Bush Field Plantground waterPFOA29.9 ppt4.0 ppt
Jun 22, 2023Finished Water Tap Bush Field Plantground waterPFOS51.0 ppt4.0 ppt
Jun 22, 2023Finished Water Tap Bush Field Plantground waterPFPeS5.4 ppt4.0 ppt
Jun 29, 2023Finished Water Tap Peachtree Orchard Plantground waterPFHxS9.1 ppt3.0 ppt
Jun 29, 2023Finished Water Tap Peachtree Orchard Plantground waterPFOS16.2 ppt4.0 ppt
Sep 6, 2023Finished Water Tap Augusta-Richmond Co. Water Plantsurface waterPFPeA3.0 ppt3.0 ppt
Sep 6, 2023Entry to Dist. System Tobacco Road - Augusta Max Hicks Filter Plantsurface waterPFPeA3.0 ppt3.0 ppt
Dec 6, 2023Finished Water Tap Peachtree Orchard Plantground waterPFHxS5.6 ppt3.0 ppt
Dec 6, 2023Finished Water Tap Peachtree Orchard Plantground waterPFOS9.4 ppt4.0 ppt
Dec 6, 2023Finished Water Tap Bush Field Plantground waterPFBS4.3 ppt3.0 ppt
Dec 6, 2023Finished Water Tap Bush Field Plantground waterPFHxA6.8 ppt3.0 ppt
Dec 6, 2023Finished Water Tap Bush Field Plantground waterPFHxS37.7 ppt3.0 ppt
Dec 6, 2023Finished Water Tap Bush Field Plantground waterPFOA23.3 ppt4.0 ppt
Dec 6, 2023Finished Water Tap Bush Field Plantground waterPFOS36.3 ppt4.0 ppt
Dec 6, 2023Finished Water Tap Bush Field Plantground waterPFPeS4.2 ppt4.0 ppt

Utility-reported context (UCMR 5 questionnaire, aggregated across sampling events): PFAS previously found at this system: yes at 14 of 14 sampling events; potential PFAS sources nearby: not known at 14 of 14 sampling events; PFAS treatment in place: no PFAS treatment at 14 of 14 sampling events.

Lead at customer taps

In the latest completed monitoring period, ending Dec 31, 2025, 9 in 10 sampled homes had lead at or below 1.4 ppb, below the 15 ppb action level that triggers utility action. None of the 14 periods on record reached it.

Action level 15 ppb015Jan 1, 2002 – Dec 31, 2002: 2.5 ppbJan 1, 2003 – Dec 31, 2003: 2.8 ppbJan 1, 2004 – Dec 31, 2004: 2.6 ppbJan 1, 2005 – Dec 31, 2005: 2.5 ppbJan 1, 2006 – Dec 31, 2006: 2.5 ppbJan 1, 2007 – Dec 31, 2009: 2.5 ppbJan 1, 2010 – Dec 31, 2012: 2.5 ppbJan 1, 2013 – Dec 31, 2015: 3.5 ppbJan 1, 2014 – Dec 31, 2016: 2 ppbJan 1, 2017 – Dec 31, 2019: 1.6 ppbJan 1, 2020 – Dec 31, 2022: 1.6 ppbJan 1, 2023 – Dec 31, 2025: 1.4 ppbDec 31, 2002Dec 31, 20251.4 ppb

In the most recent completed lead monitoring period, ending Dec 31, 2025, the 90th-percentile lead result at customer taps was 1.4 ppb, below the action level of 15 ppb (14 monitoring periods on record, none at the action level). The 90th percentile is the value that 9 in 10 sampled homes were at or below. Values are in parts per billion (ppb).

Monitoring periodMetal90th percentileAction levelStatus
Jan 1, 2023 – Dec 31, 2025Lead1.4 ppb15 ppbbelow the action level
Jan 1, 2020 – Dec 31, 2022Lead1.6 ppb15 ppbbelow the action level
Jan 1, 2017 – Dec 31, 2019Lead1.6 ppb15 ppbbelow the action level
Jan 1, 2014 – Dec 31, 2016Lead2 ppb15 ppbbelow the action level
Jan 1, 2013 – Dec 31, 2015Lead3.5 ppb15 ppbbelow the action level
Jan 1, 2010 – Dec 31, 2012Lead2.5 ppb15 ppbbelow the action level
Jan 1, 2007 – Dec 31, 2009Lead2.5 ppb15 ppbbelow the action level
Jan 1, 2006 – Dec 31, 2006Lead2.5 ppb15 ppbbelow the action level
Jan 1, 2005 – Dec 31, 2005Lead2.5 ppb15 ppbbelow the action level
Jan 1, 2004 – Dec 31, 2004Lead2.6 ppb15 ppbbelow the action level
Jan 1, 2003 – Dec 31, 2003Lead2.8 ppb15 ppbbelow the action level
Jan 1, 2002 – Dec 31, 2002Lead2.5 ppb15 ppbbelow the action level
Show all 14 monitoring periods on record
Monitoring periodMetal90th percentileAction levelStatus
Jan 1, 2023 – Dec 31, 2025Lead1.4 ppb15 ppbbelow the action level
Jan 1, 2020 – Dec 31, 2022Lead1.6 ppb15 ppbbelow the action level
Jan 1, 2017 – Dec 31, 2019Lead1.6 ppb15 ppbbelow the action level
Jan 1, 2014 – Dec 31, 2016Lead2 ppb15 ppbbelow the action level
Jan 1, 2013 – Dec 31, 2015Lead3.5 ppb15 ppbbelow the action level
Jan 1, 2010 – Dec 31, 2012Lead2.5 ppb15 ppbbelow the action level
Jan 1, 2007 – Dec 31, 2009Lead2.5 ppb15 ppbbelow the action level
Jan 1, 2006 – Dec 31, 2006Lead2.5 ppb15 ppbbelow the action level
Jan 1, 2005 – Dec 31, 2005Lead2.5 ppb15 ppbbelow the action level
Jan 1, 2004 – Dec 31, 2004Lead2.6 ppb15 ppbbelow the action level
Jan 1, 2003 – Dec 31, 2003Lead2.8 ppb15 ppbbelow the action level
Jan 1, 2002 – Dec 31, 2002Lead2.5 ppb15 ppbbelow the action level
Jul 1, 2001 – Dec 31, 2001Lead2.8 ppb15 ppbbelow the action level
Jan 1, 2001 – Jun 30, 2001Lead3.3 ppb15 ppbbelow the action level

Drinking water violations since Sep 3, 2016

EPA lists no drinking-water violations for this utility since Sep 3, 2016.

EPA's SDWIS database lists no drinking water violations for this utility since Sep 3, 2016.

None on file.

Sanitary surveys and site visits

Most recent state inspection: Sep 23, 2025 (sanitary survey); 2 visits since Sep 3, 2021.

What you can do about these results

Filters certified to reduce PFOA and PFOS

EPA testing found 7 PFAS above reporting levels in this utility's water.

Look for NSF/ANSI 53 (activated carbon) or NSF/ANSI 58 (reverse osmosis) certification that names PFOA/PFOS reduction.

ZIP codes served

Sources

Data vintage: EPA UCMR 5 occurrence data, samples collected 2023-01-03 – 2026-06-17, final release, August 2026 (file dated Aug 28, 2026); EPA SDWIS via ECHO, 2026Q2 extract (file dated Jul 9, 2026); EPA service-area boundaries v3.0; Census 2020 ZCTAs. Page generated 2026-09-03.

Keep exploring

Every record tells
part of the story.

Find a place. Read the measurements.
Understand the context.

Explore water records