Tap Water Lookup

EPA system OH2504412 · Ohio

Columbus Public Water System: 6 PFAS found; PFOA averaged 1.3 ppt, below the 4.0 ppt limit

System ID OH2504412; community water system; Ohio; source: surface water; serves 1,305,946 people via 287,233 connections; status: active

In focus1,305,946people served, EPA registry
Public records. Clearer context.
Highest result against its EPA referencePFOA
PFOA: 1.3 ppt; MCL 4.0 ppt. highest complete sampling-location average.1.3 pptMCL: 4.0 ppt

highest complete sampling-location average; sampled February 2024–November 2024. Source: EPA UCMR 5 final release, August 2026.

Columbus Public Water System is a local-government-owned community water system in Ohio serving about 1,305,946 people, matched to 53 ZIP codes.

1.3 ppt
PFOA, highest complete-set average
4 of 4 results at the highest location; highest single sample 5.3 ppt
MCL 4.0 ppt · below the MCL
< 4.0 ppt
PFOS, highest complete-set average
10 samples, none above the reporting level
MCL 4.0 ppt · not detected above the reporting level
< 9 ppb
Lithium, highest single sample
10 samples, none above the reporting level
health reference level 10 ppb · not detected above the reporting level
6 / 29
PFAS found above the reporting level
300 results, 3 entry points
0 at or above an MCL on the average basis
1.2 ppb
Lead 90th percentile
period ending Dec 31, 2023
action level 15 ppb · below the action level
0
health-based violations since Sep 3, 2016
0 violations in total

PFAS treatment declared to EPA: None declared (10 of 10 sampling events) · PFAS found before UCMR 5: Yes, at 10 of 10 sampling events

What EPA says about what was found

  • PFOA EPA set the health goal (MCLG) for PFOA at zero. EPA's 2024 rule cites its health effects assessment linking PFOA exposure to certain cancers, immune and developmental effects, and changes in cholesterol. EPA source
  • PFHxA EPA's 2023 IRIS assessment for PFHxA cites developmental, liver and blood effects in animal studies. EPA source
  • PFBS EPA's 2021 PFBS toxicity assessment cites thyroid, kidney and developmental effects in animal studies. EPA source
  • PFBA EPA's 2022 IRIS assessment for PFBA cites thyroid, liver and developmental effects in animal studies. EPA source

Quoted from EPA assessments. This site adds no health claims of its own.

PFAS and lithium: what EPA's national survey found

EPA tested this water for 30 substances and found 6. PFOA averaged 1.3 ppt where EPA's limit is 4.0 ppt. That PFOA result is higher than 88% of the 10,307 water systems EPA tested for it.

Between February 2024 and November 2024, EPA's UCMR 5 program tested 300 samples from 3 sampling locations for 30 contaminants (29 PFAS plus lithium). 6 were detected above the reporting level in at least one sample. Averaged over a complete monitoring set, the highest sampling location for PFOA was 1.3 ppt, below the MCL of 4.0 ppt that applies from 2029 (highest single sample 5.3 ppt).

Result EPA comparesNot detected, shown at the reporting levelEPA reference value, at the middle of each row's scale
ContaminantResult against the EPA referenceResultStatus
PFPeAhighest single sample
14.2 ppt
detected; no EPA reference value
PFHpAhighest single sample
4.3 ppt
detected; no EPA reference value
PFOAcomplete-set average
1.3 ppt
below the MCL
PFHxAhighest single sample
18.2 ppt
below the screening level
PFBShighest single sample
11.1 ppt
below the health-based water concentration
PFBAhighest single sample
17.0 ppt
below the screening level
Show the 24 contaminants not detected above the reporting level
11Cl-PF3OUdSnot detected · reporting level 5.0 ppt
< 5.0 ppt
not detected above the reporting level
4:2 FTSnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
6:2 FTSnot detected · reporting level 5.0 ppt
< 5.0 ppt
not detected above the reporting level
8:2 FTSnot detected · reporting level 5.0 ppt
< 5.0 ppt
not detected above the reporting level
9Cl-PF3ONSnot detected · reporting level 2.0 ppt
< 2.0 ppt
not detected above the reporting level
ADONAnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
HFPO-DA (GenX)not detected · reporting level 5.0 ppt
< 5.0 ppt
not detected above the reporting level
Lithiumnot detected · reporting level 9 ppb
< 9 ppb
not detected above the reporting level
NEtFOSAAnot detected · reporting level 5.0 ppt
< 5.0 ppt
not detected above the reporting level
NFDHAnot detected · reporting level 20.0 ppt
< 20.0 ppt
not detected above the reporting level
NMeFOSAAnot detected · reporting level 6.0 ppt
< 6.0 ppt
not detected above the reporting level
PFDAnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
PFDoAnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
PFEESAnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
PFHpSnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
PFHxSnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
PFMBAnot detected · reporting level 3.0 ppt
< 3.0 ppt
not detected above the reporting level
PFMPAnot detected · reporting level 4.0 ppt
< 4.0 ppt
not detected above the reporting level
PFNAnot detected · reporting level 4.0 ppt
< 4.0 ppt
not detected above the reporting level
PFOSnot detected · reporting level 4.0 ppt
< 4.0 ppt
not detected above the reporting level
PFPeSnot detected · reporting level 4.0 ppt
< 4.0 ppt
not detected above the reporting level
PFTAnot detected · reporting level 8.0 ppt
< 8.0 ppt
not detected above the reporting level
PFTrDAnot detected · reporting level 7.0 ppt
< 7.0 ppt
not detected above the reporting level
PFUnAnot detected · reporting level 2.0 ppt
< 2.0 ppt
not detected above the reporting level
Full table: samples, detections, highest single sample, complete-set average and sampling dates for all 30 contaminants
ContaminantSamplesDetectionsHighest single sampleComplete-set average (results used)EPA referenceStatusSampled
PFPeA10314.2 ppt4.3 ppt (4 of 4)none setdetected; no EPA reference valueFebruary 2024 – November 2024
PFHpA1014.3 ppt1.1 ppt (4 of 4)none setdetected; no EPA reference valueFebruary 2024 – November 2024
PFOA1015.3 ppt1.3 ppt (4 of 4)4.0 ppt MCL · compared on the complete-set averagebelow the MCLFebruary 2024 – November 2024
PFHxA10318.2 ppt6.7 ppt (4 of 4)3,000 ppt screening level · compared on the highest samplebelow the screening levelFebruary 2024 – November 2024
PFBS10111.1 ppt2.8 ppt (4 of 4)2,000 ppt health-based water concentration · compared on the highest samplebelow the health-based water concentrationFebruary 2024 – November 2024
PFBA10417.0 ppt7.4 ppt (4 of 4)6,000 ppt screening level · compared on the highest samplebelow the screening levelFebruary 2024 – November 2024
11Cl-PF3OUdS100< 5.0 pptnone setnot detected above the reporting levelFebruary 2024 – November 2024
4:2 FTS100< 3.0 pptnone setnot detected above the reporting levelFebruary 2024 – November 2024
6:2 FTS100< 5.0 pptnone setnot detected above the reporting levelFebruary 2024 – November 2024
8:2 FTS100< 5.0 pptnone setnot detected above the reporting levelFebruary 2024 – November 2024
9Cl-PF3ONS100< 2.0 pptnone setnot detected above the reporting levelFebruary 2024 – November 2024
ADONA100< 3.0 pptnone setnot detected above the reporting levelFebruary 2024 – November 2024
HFPO-DA (GenX)100< 5.0 ppt10.0 ppt MCL (rescission proposed) · compared on the complete-set averagenot detected above the reporting levelFebruary 2024 – November 2024
Lithium100< 9 ppb10 ppb health reference level · compared on the highest samplenot detected above the reporting levelFebruary 2024 – November 2024
NEtFOSAA100< 5.0 pptnone setnot detected above the reporting levelFebruary 2024 – November 2024
NFDHA100< 20.0 pptnone setnot detected above the reporting levelFebruary 2024 – November 2024
NMeFOSAA100< 6.0 pptnone setnot detected above the reporting levelFebruary 2024 – November 2024
PFDA100< 3.0 pptnone setnot detected above the reporting levelFebruary 2024 – November 2024
PFDoA100< 3.0 pptnone setnot detected above the reporting levelFebruary 2024 – November 2024
PFEESA100< 3.0 pptnone setnot detected above the reporting levelFebruary 2024 – November 2024
PFHpS100< 3.0 pptnone setnot detected above the reporting levelFebruary 2024 – November 2024
PFHxS100< 3.0 ppt10.0 ppt MCL (rescission proposed) · compared on the complete-set averagenot detected above the reporting levelFebruary 2024 – November 2024
PFMBA100< 3.0 pptnone setnot detected above the reporting levelFebruary 2024 – November 2024
PFMPA100< 4.0 pptnone setnot detected above the reporting levelFebruary 2024 – November 2024
PFNA100< 4.0 ppt10.0 ppt MCL (rescission proposed) · compared on the complete-set averagenot detected above the reporting levelFebruary 2024 – November 2024
PFOS100< 4.0 ppt4.0 ppt MCL · compared on the complete-set averagenot detected above the reporting levelFebruary 2024 – November 2024
PFPeS100< 4.0 pptnone setnot detected above the reporting levelFebruary 2024 – November 2024
PFTA100< 8.0 pptnone setnot detected above the reporting levelFebruary 2024 – November 2024
PFTrDA100< 7.0 pptnone setnot detected above the reporting levelFebruary 2024 – November 2024
PFUnA100< 2.0 pptnone setnot detected above the reporting levelFebruary 2024 – November 2024
UCMR 5 is a one-time national monitoring survey. Its results do not indicate compliance or non-compliance with the PFAS Maximum Contaminant Levels, which are enforced on running annual averages and take effect in 2029 (EPA has proposed allowing extensions to 2031). A single result above a limit on this page is a measurement, not a violation.

Sampling-point average: mean of a location's two (ground water) or four (surface water) UCMR 5 results with non-detects counted as zero, EPA's method for comparing UCMR 5 data to the PFAS MCLs. EPA rounds to the reference value's significant digits before deciding whether an average is "greater than" an MCL (PFOA/PFOS averages count as above 4.0 ng/L only from 4.05 ng/L; lithium results count as above the 10 ppb reference only from 15 ppb). This site does not apply that rounding: "at or above" here means the measured value is numerically at or above the reference.

Every detection by sampling location (13 results)
DateSampling locationSource waterContaminantResultReporting level
Feb 13, 2024Entry Point to Dist. System Dublin Road WTPsurface waterPFBA5.2 ppt5.0 ppt
Feb 13, 2024Entry Point to Dist. System Dublin Road WTPsurface waterPFHxA4.5 ppt3.0 ppt
Feb 13, 2024Entry Point to Dist. System Parsons Ave. WTPground waterPFBA6.0 ppt5.0 ppt
Feb 13, 2024Entry Point to Dist. System Parsons Ave. WTPground waterPFPeA3.3 ppt3.0 ppt
May 21, 2024Entry Point to Dist. System Dublin Road WTPsurface waterPFBA7.3 ppt5.0 ppt
May 21, 2024Entry Point to Dist. System Dublin Road WTPsurface waterPFHxA4.1 ppt3.0 ppt
May 21, 2024Entry Point to Dist. System Dublin Road WTPsurface waterPFPeA3.1 ppt3.0 ppt
Nov 20, 2024Entry Point to Dist. System Dublin Road WTPsurface waterPFBA17.0 ppt5.0 ppt
Nov 20, 2024Entry Point to Dist. System Dublin Road WTPsurface waterPFBS11.1 ppt3.0 ppt
Nov 20, 2024Entry Point to Dist. System Dublin Road WTPsurface waterPFHpA4.3 ppt3.0 ppt
Nov 20, 2024Entry Point to Dist. System Dublin Road WTPsurface waterPFHxA18.2 ppt3.0 ppt
Nov 20, 2024Entry Point to Dist. System Dublin Road WTPsurface waterPFOA5.3 ppt4.0 ppt
Nov 20, 2024Entry Point to Dist. System Dublin Road WTPsurface waterPFPeA14.2 ppt3.0 ppt

Utility-reported context (UCMR 5 questionnaire, aggregated across sampling events): PFAS previously found at this system: yes at 10 of 10 sampling events; potential PFAS sources nearby: no at 6 of 10 sampling events, yes at 4 of 10 sampling events; PFAS treatment in place: no PFAS treatment at 10 of 10 sampling events.

Lead and copper at customer taps

In the latest completed monitoring period, ending Dec 31, 2023, 9 in 10 sampled homes had lead at or below 1.2 ppb, below the 15 ppb action level that triggers utility action. The action level has been reached in 3 of the 17 periods on record.

Action level 15 ppb015Jan 1, 1999 – Jun 30, 1999: 1 ppbJan 1, 2000 – Dec 31, 2000: 1 ppbJan 1, 2001 – Dec 31, 2001: 1 ppbJan 1, 2002 – Dec 31, 2002: 1 ppbJun 1, 2005 – Sep 30, 2005: 1,000 ppbJan 1, 2005 – Dec 31, 2007: 0 ppbJan 1, 2008 – Dec 31, 2010: 0 ppbJan 1, 2009 – Dec 31, 2011: 0 ppbJan 1, 2012 – Dec 31, 2014: 0 ppbJan 1, 2015 – Dec 31, 2017: 0 ppbJan 1, 2018 – Dec 31, 2020: 0 ppbJan 1, 2021 – Dec 31, 2023: 1.2 ppbJun 30, 1999Dec 31, 20231.2 ppb

In the most recent completed lead monitoring period, ending Dec 31, 2023, the 90th-percentile lead result at customer taps was 1.2 ppb, below the action level of 15 ppb; 3 of the 17 monitoring periods on record reached the action level. The 90th percentile is the value that 9 in 10 sampled homes were at or below. Values are in parts per billion (ppb).

Monitoring periodMetal90th percentileAction levelStatus
Jan 1, 2021 – Dec 31, 2023Lead1.2 ppb15 ppbbelow the action level
Jan 1, 2018 – Dec 31, 2020Lead0 ppb15 ppbbelow the action level
Jan 1, 2015 – Dec 31, 2017Lead0 ppb15 ppbbelow the action level
Jan 1, 2012 – Dec 31, 2014Lead0 ppb15 ppbbelow the action level
Jan 1, 2009 – Dec 31, 2011Lead0 ppb15 ppbbelow the action level
Jan 1, 2008 – Dec 31, 2010Lead0 ppb15 ppbbelow the action level
Jan 1, 2005 – Dec 31, 2007Lead0 ppb15 ppbbelow the action level
Jun 1, 2005 – Sep 30, 2005Copper58,700 ppb1,300 ppbat or above the action level
Jun 1, 2005 – Sep 30, 2005Lead1,000 ppb15 ppbat or above the action level
Jan 1, 2002 – Dec 31, 2002Lead1 ppb15 ppbbelow the action level
Jan 1, 2001 – Dec 31, 2001Lead1 ppb15 ppbbelow the action level
Jan 1, 2000 – Dec 31, 2000Lead1 ppb15 ppbbelow the action level
Show all 18 monitoring periods on record
Monitoring periodMetal90th percentileAction levelStatus
Jan 1, 2021 – Dec 31, 2023Lead1.2 ppb15 ppbbelow the action level
Jan 1, 2018 – Dec 31, 2020Lead0 ppb15 ppbbelow the action level
Jan 1, 2015 – Dec 31, 2017Lead0 ppb15 ppbbelow the action level
Jan 1, 2012 – Dec 31, 2014Lead0 ppb15 ppbbelow the action level
Jan 1, 2009 – Dec 31, 2011Lead0 ppb15 ppbbelow the action level
Jan 1, 2008 – Dec 31, 2010Lead0 ppb15 ppbbelow the action level
Jan 1, 2005 – Dec 31, 2007Lead0 ppb15 ppbbelow the action level
Jun 1, 2005 – Sep 30, 2005Copper58,700 ppb1,300 ppbat or above the action level
Jun 1, 2005 – Sep 30, 2005Lead1,000 ppb15 ppbat or above the action level
Jan 1, 2002 – Dec 31, 2002Lead1 ppb15 ppbbelow the action level
Jan 1, 2001 – Dec 31, 2001Lead1 ppb15 ppbbelow the action level
Jan 1, 2000 – Dec 31, 2000Lead1 ppb15 ppbbelow the action level
Jan 1, 1999 – Jun 30, 1999Lead1 ppb15 ppbbelow the action level
Jul 1, 1998 – Dec 31, 1998Lead3 ppb15 ppbbelow the action level
Jan 1, 1998 – Jun 30, 1998Lead4 ppb15 ppbbelow the action level
Jul 1, 1997 – Dec 31, 1997Lead3 ppb15 ppbbelow the action level
Jan 1, 1997 – Jun 30, 1997Lead33 ppb15 ppbat or above the action level
Jul 1, 1992 – Dec 31, 1992Lead16 ppb15 ppbat or above the action level

Drinking water violations since Sep 3, 2016

EPA lists no drinking-water violations for this utility since Sep 3, 2016.

EPA's SDWIS database lists no drinking water violations for this utility since Sep 3, 2016.

None on file.

Sanitary surveys and site visits

Most recent state inspection: Oct 7, 2025 (reason not recorded); 104 visits since Sep 3, 2021.

What you can do about these results

Filters certified to reduce PFOA and PFOS

EPA testing found 6 PFAS above reporting levels in this utility's water.

Look for NSF/ANSI 53 (activated carbon) or NSF/ANSI 58 (reverse osmosis) certification that names PFOA/PFOS reduction.

Filters certified for lead reduction

3 of this utility's 17 lead monitoring periods on record reached the 15 ppb action level (most recent 90th percentile 1.2 ppb).

NSF/ANSI 53 with a lead-reduction claim, or NSF/ANSI 58 reverse osmosis. Lead comes from plumbing, so a point-of-use filter at the kitchen tap is the relevant type.

ZIP codes served

Sources

Data vintage: EPA UCMR 5 occurrence data, samples collected 2023-01-03 – 2026-06-17, final release, August 2026 (file dated Aug 28, 2026); EPA SDWIS via ECHO, 2026Q2 extract (file dated Jul 9, 2026); EPA service-area boundaries v3.0; Census 2020 ZCTAs. Page generated 2026-09-03.

Keep exploring

Every record tells
part of the story.

Find a place. Read the measurements.
Understand the context.

Explore water records