EPA system WA5305575 · Washington
Bellevue City of: No PFAS or lithium found in EPA testing
Bellevue City of is a local-government-owned community water system in Washington serving about 321,349 people, matched to 6 ZIP codes.
MCL 4.0 ppt · not detected above the reporting level
MCL 4.0 ppt · not detected above the reporting level
health reference level 10 ppb · not detected above the reporting level
PFAS and lithium: what EPA's national survey found
EPA tested this water for 30 substances and found none of them at levels its laboratories can measure.
Between January 2024 and October 2024, EPA's UCMR 5 program tested 240 samples from 2 sampling locations for 30 contaminants (29 PFAS plus lithium). None were found above their minimum reporting levels.
Show the 30 contaminants not detected above the reporting level
Full table: samples, detections, highest single sample, complete-set average and sampling dates for all 30 contaminants
| Contaminant | Samples | Detections | Highest single sample | Complete-set average (results used) | EPA reference | Status | Sampled |
|---|---|---|---|---|---|---|---|
| 11Cl-PF3OUdS | 8 | 0 | < 5.0 ppt | — | none set | not detected above the reporting level | January 2024 – October 2024 |
| 4:2 FTS | 8 | 0 | < 3.0 ppt | — | none set | not detected above the reporting level | January 2024 – October 2024 |
| 6:2 FTS | 8 | 0 | < 5.0 ppt | — | none set | not detected above the reporting level | January 2024 – October 2024 |
| 8:2 FTS | 8 | 0 | < 5.0 ppt | — | none set | not detected above the reporting level | January 2024 – October 2024 |
| 9Cl-PF3ONS | 8 | 0 | < 2.0 ppt | — | none set | not detected above the reporting level | January 2024 – October 2024 |
| ADONA | 8 | 0 | < 3.0 ppt | — | none set | not detected above the reporting level | January 2024 – October 2024 |
| HFPO-DA (GenX) | 8 | 0 | < 5.0 ppt | — | 10.0 ppt MCL (rescission proposed) · compared on the complete-set average | not detected above the reporting level | January 2024 – October 2024 |
| Lithium | 8 | 0 | < 9 ppb | — | 10 ppb health reference level · compared on the highest sample | not detected above the reporting level | January 2024 – October 2024 |
| NEtFOSAA | 8 | 0 | < 5.0 ppt | — | none set | not detected above the reporting level | January 2024 – October 2024 |
| NFDHA | 8 | 0 | < 20.0 ppt | — | none set | not detected above the reporting level | January 2024 – October 2024 |
| NMeFOSAA | 8 | 0 | < 6.0 ppt | — | none set | not detected above the reporting level | January 2024 – October 2024 |
| PFBA | 8 | 0 | < 5.0 ppt | — | 6,000 ppt screening level · compared on the highest sample | not detected above the reporting level | January 2024 – October 2024 |
| PFBS | 8 | 0 | < 3.0 ppt | — | 2,000 ppt health-based water concentration · compared on the highest sample | not detected above the reporting level | January 2024 – October 2024 |
| PFDA | 8 | 0 | < 3.0 ppt | — | none set | not detected above the reporting level | January 2024 – October 2024 |
| PFDoA | 8 | 0 | < 3.0 ppt | — | none set | not detected above the reporting level | January 2024 – October 2024 |
| PFEESA | 8 | 0 | < 3.0 ppt | — | none set | not detected above the reporting level | January 2024 – October 2024 |
| PFHpA | 8 | 0 | < 3.0 ppt | — | none set | not detected above the reporting level | January 2024 – October 2024 |
| PFHpS | 8 | 0 | < 3.0 ppt | — | none set | not detected above the reporting level | January 2024 – October 2024 |
| PFHxA | 8 | 0 | < 3.0 ppt | — | 3,000 ppt screening level · compared on the highest sample | not detected above the reporting level | January 2024 – October 2024 |
| PFHxS | 8 | 0 | < 3.0 ppt | — | 10.0 ppt MCL (rescission proposed) · compared on the complete-set average | not detected above the reporting level | January 2024 – October 2024 |
| PFMBA | 8 | 0 | < 3.0 ppt | — | none set | not detected above the reporting level | January 2024 – October 2024 |
| PFMPA | 8 | 0 | < 4.0 ppt | — | none set | not detected above the reporting level | January 2024 – October 2024 |
| PFNA | 8 | 0 | < 4.0 ppt | — | 10.0 ppt MCL (rescission proposed) · compared on the complete-set average | not detected above the reporting level | January 2024 – October 2024 |
| PFOA | 8 | 0 | < 4.0 ppt | — | 4.0 ppt MCL · compared on the complete-set average | not detected above the reporting level | January 2024 – October 2024 |
| PFOS | 8 | 0 | < 4.0 ppt | — | 4.0 ppt MCL · compared on the complete-set average | not detected above the reporting level | January 2024 – October 2024 |
| PFPeA | 8 | 0 | < 3.0 ppt | — | none set | not detected above the reporting level | January 2024 – October 2024 |
| PFPeS | 8 | 0 | < 4.0 ppt | — | none set | not detected above the reporting level | January 2024 – October 2024 |
| PFTA | 8 | 0 | < 8.0 ppt | — | none set | not detected above the reporting level | January 2024 – October 2024 |
| PFTrDA | 8 | 0 | < 7.0 ppt | — | none set | not detected above the reporting level | January 2024 – October 2024 |
| PFUnA | 8 | 0 | < 2.0 ppt | — | none set | not detected above the reporting level | January 2024 – October 2024 |
Sampling-point average: mean of a location's two (ground water) or four (surface water) UCMR 5 results with non-detects counted as zero, EPA's method for comparing UCMR 5 data to the PFAS MCLs. EPA rounds to the reference value's significant digits before deciding whether an average is "greater than" an MCL (PFOA/PFOS averages count as above 4.0 ng/L only from 4.05 ng/L; lithium results count as above the 10 ppb reference only from 15 ppb). This site does not apply that rounding: "at or above" here means the measured value is numerically at or above the reference.
Utility-reported context (UCMR 5 questionnaire, aggregated across sampling events): PFAS previously found at this system: yes at 8 of 8 sampling events; potential PFAS sources nearby: no at 8 of 8 sampling events; PFAS treatment in place: no PFAS treatment at 8 of 8 sampling events.
Lead at customer taps
EPA's database holds no usable lead result for Bellevue City of.
No lead and copper 90th-percentile results are on file in SDWIS. The 90th percentile is the value that 9 in 10 sampled homes were at or below. Values are in parts per billion (ppb).
Drinking water violations since Sep 3, 2016
EPA lists no drinking-water violations for this utility since Sep 3, 2016.
EPA's SDWIS database lists no drinking water violations for this utility since Sep 3, 2016.
None on file.
Sanitary surveys and site visits
Most recent state inspection: Nov 24, 2025 (sanitary survey); 1 visit since Sep 3, 2021.
What you can do about these results
Test your own tap
EPA results are measured where water enters the distribution system, not at your tap.
A certified-lab mail-in kit reports lead and PFAS from your own faucet; strip tests do not detect PFAS.
ZIP codes served
Sources
Data vintage: EPA UCMR 5 occurrence data, samples collected 2023-01-03 – 2026-06-17, final release, August 2026 (file dated Aug 28, 2026); EPA SDWIS via ECHO, 2026Q2 extract (file dated Jul 9, 2026); EPA service-area boundaries v3.0; Census 2020 ZCTAs. Page generated 2026-09-03.
- EPA ECHO detailed facility report
- EPA UCMR 5 Data Finder
- EPA service-area boundary: modeled, 34.5 sq mi